Pertu only find plc by address same device_Pertu v13 can't find device

Botu as through not know the originalplcThe plc can't be found with the ip address of the

: How is it possible for this problem to occur! That at the beginning of the new PLC everyone does not know the IP address of the PLC you say how it is possible!

Selecting Show all compatible devices is not found either. What can I do to fix this? Thank you!

Hardware connections, your own computer's NIC settings, Protherm's NIC selection, and interfaces are all to be found.

PLC with Protherm can not find I have not met, touch screen with Protherm can not find the IP this is met, generally re-power, change the IP address can be found.

Answererer:

Vegetable Legs Riding Vegetable Bikes for Groceries - Assistant Engineer Level 8

2016-11-12 18:29:58

Currently it is not possible to connect plc according to MAC address, maybe it will be possible soon. Many touch screens are connected according to the device name configuration.

Answererer:

Moon, Rain, Wind and Cloud - Intermediate Technician Level 6

2016-11-12 19:44:14

1. First of all, it is recommended to set the IP address of the computer to the same network segment, and then spell out the network to see if there is any problem with the hardware connection.

2. Set up your computer's PG/PC excuse and check your wired network card.

3. You can search for all devices in Boto, there is an option bar for online access. See attachment

Answer: Tang Wenbo - Graduate Practitioner Level 4

2016-11-13 14:16:38

The pc side uses the IP of the automatic connection. Configure unspecified plc and select online for hardware search. Try it thanks.

Answererer:

Forget 817 - Junior Technician Level 5

2016-11-13 16:13:55

Take a look at the online hardware search in Boto

Answererer:

xf123456 - Assistant Engineer Level 8

2016-11-13 22:52:53

Select the correct PG/PC interface, then tap online search, the system will prompt not in a network segment, is it set in the same network segment, the motor is, it should be able to connect.

Or configure the PLC and select a non-specific CPU when selecting the CPU.

Answer: young and gently handsome - Graduate Practitioner Level 4

2016-11-16 10:23:47